Chapter 4: Cabling the Switch
7000 Series 1 RU – Gen 2 Quick Start Guide PDOC-00019-13 15
4.1.2 DC Power Supply
The DC power supply connects to a circuit that provides 40-72 VDC and 13.9–7.72 A. Figure 16 displays
the DC power supply with the terminal cover in place (left illustration) and with the terminal cover
removed (right illustration).
Ensure the wires connecting the DC power supply to the power source meet the following:
DC Input Wire Size: AWG 14 (2.0 mm
2
) or larger as appropriate
Safety Ground Wire Size: AWG 14 (2.0 mm
2
) or larger as appropriate
Wire Terminal (Lug): ring or spade, 14-16 AWG, #8 (4 mm) screw
Overcurrent protection: 20 A.
Important! Ensure power is removed from DC circuits before performing any installation actions. Locate circuit
breakers or fuses on DC power lines servicing the circuits. Turn off the power line circuits or remove
the fuses.
To connect a DC power supply to power source:
Step 1 Remove the terminal cover to expose the connectors on the right side of the module (Figure 16).
Step 2 Attach the appropriate lugs to the source DC wires.
Use DC cables with either insulated crimp-on spade lugs or insulated crimp-on ring connectors.
Important! Wire size must comply with local and national requirements and electrical codes. Use only copper wire.
Step 3 Connect the DC-input wires to the terminal block in this order:
1. Ground cable to the ground connector on the terminal block.
2. Negative (–) source DC cable to the negative (–) connector on the terminal block.
3. Positive (+) source DC cable to the positive (+) connector on the terminal block.
Important! Apply the ground connection first during installation and remove last when removing power.
Step 4 Replace the terminal cover.
4.2 Connecting Serial and Management Cables
The accessory kit includes the following cables:
RJ-45 to DB-9 serial adapter cable.
RJ-45 Ethernet cable.
Figure 16: DC Power Supply – terminal cover in place (left); terminal cover removed (right)
Ground
+
Vista de pagina 14